HV Equipment

 

DTA 100 Inline

Continuous Inline test of breakdown strength
The BAUR Oil Tester 100 Inline

Main Features

  • Inline insulating liquid test in oil preparation systems
  • Quality assurance during production processes
  • Improved, easy oil sample handling
  • Integration in existing production process control possible

Permanent and safe analysis of insulating oils with BAUR DTA 100 C Inline
The BAUR DTA 100 C Inline is a high performance and reliable oil tester for continuous testing of the breakdown strength of insulating oils during production (Inline tests). The combination of extremely short switch-off times during breakdowns and the easy oil sample handling facilitate high quality statements and conclusions on the insulating oil quality. Standard connections for oil inlet and outlet and the possibility to integrate in existing production processes (e.g. PLC control) enable easy and automated oil testing. In addition to these properties, the archiving and clear allocation of measurement results is greatly simplified and made faster when combined with the BAUR software ITS Lite owing to the fully automated measurement data export. 


FACTS:

  • Test voltages up to 100 kV
  • High performance oil tester for testing breakdown strength of insulating oils during production (Inline test)
  • Suitable for portable and stationary oil preparation systems specialized laboratories
  • Switch-off time below 10 microseconds for reliable and reproducible results through multiple measurements
  • Measurements without air inflow due to high quality test vessels
  • Precise setting of electrode distance
  • Clear breakdown detection with measurement principle directly on the high voltage side
  • Repeatable breakdown measurements even on silicone oils and ester fluids
  • Automatic self-test with HV output voltage test
  • Fully automatic measuring sequences from 19 programmed test standards (adapted for operation without stirring)
  • Oil-proof membrane keyboard, easy to read LCD display, and integrated printer
  • Built-in sensor for temperature measurement of the insulating oil
  • High quality test vessels
  • EMC shield to prevent damage to IT infrastructure

Optimum data management possibilities 

Proper archiving of the measurement results is essential for the analysis of insulating oil. The DTA 100 Inline allows 3 different possibilities to archive the results:

  • Integrated printer for immediate print out of the results
  • ITS Lite software: allows structured storage of measurement results in .pdf and/or .txt files on any PC/laptop that is connected to the DPA 75 C. This is ideal for use in a laboratory environment.
  • Report Manager: allows automatic storage of measurement results in .pdf and/or .txt files on an external device that can be exported at a later time using an USB stick. Ideal for when a PC/laptop cannot be used in a testing laboratory.

Download ITS Lite

 

 

Request a Quote Here